OVERHEAD AERIAL

HDPE SPACER

Made of high-density polyethylene (HDPE)

 

NOMINAL VOLTAGE:
15 Kv

 

LOWEST VOLTAGE APPLIED AT INDUSTRIAL FREQUENCY :

70Kv


VOLTAGE AT FREQUENCYINDUSTRIAL UNDER RAIN (1 MINUTE):

(1 MINUTO):

34Kv

PIN INSULATOR

Creepage distance:
310 mm
arc distance on dry:
172mm
Mechanical strength in cantilever:
13 kN
VOLTAGE AT FREQUENCYINDUSTRIAL UNDER WET:
40 kV
drilling voltage
95 kV
maximum operating voltage:
15 kV

ANTI-SWAY BRACKET

It is designed to be used with 15kv HDPE Spacer


  • Reduces cable sway in the spacer
  • Maintains spacer distance from the post when the net is at small angles
  • Produced in high-density polyethylene for stresses of 15kV

OVERVOLTAGE PROTECTION BOX

MAXIMUM OPERATING VOLTAGE Uc:
150 V
Reference Current:
1mA DC
Reference voltage

222-270 V
MAXIMUM SHORT CIRCUIT CURRENT:

50ka

DPS SECONDARY DISTRIBUTION NETWORK

MODEL:
150V 40Ka
MAXIMUM CONTINUOUS OPERATING VOLTAGE
150V
NOMINAL CURRENT OF 8/20 Us
300A
MAXIMUM OVERCURRENT CURRENT AT 8/20Us:
40Ka
MAXIMUM ENERGY ABSORBED AT 10/1000Us
720 J
MAXIMUM POWER DISSIPATION
1.4 W

CABLE CLAMP CONNECTOR

high-strength die-cast aluminum terminal for joining a wide range of cables

 

Clamping iron fittings: 1/2 in

 

Type of cable: ACSR, aluminum and copp

 

CLAMPING TORQUE: 54.2 n*M (480lb*in)

 

Norm: NTC 2155, NEMA CC1 y RETIE

 

Surface treatment for use in areas with high corrosion levels